FREE SHIPPING ON ORDERS OVER $70
Previous
Previous Product Image

ANTSPACE HW5

$33.00
Next

ANTSPACE AZ

$366.00
Next Product Image

ANTSPACE HK3

$23.00

Add to Wishlist
Add to Wishlist
Category:
Trust Badge Image

Description

Specifications

Specification Details For ANTSPACE HK3
Product Overview Value

Version ANTSPACE HK3
Dimensions (l*w*h), mm 6058*2438*2896
Miner capacity 210 units -S19 Hyd. & S21 Hyd. Series miner
Container certification China Classification Society Certification
Safety certification North America/Standards: NFPA 79:2021, UL 508A:2018 R8.21,
CSA C22.2 No. 14-18,ANSI/ISO 12100:2012
EU/Standards: EN ISO 12100, EN 60204-1
Operating power, kW 1047~1050
PUE(Power usage effectiveness) 1.022 (Excluding cooling tower)/1.036 (Including cooling tower)
Input voltage and frequency 415V±5% 60Hz (North America)
400V±5% 50Hz (EU、Middle East)

Detailed Characteristics Value
Shipping weight, T 8
Operating weight, T 12
Main switch of power distribution cabinets, A 1200(North America)
1250(EU、Middle East)
Rated current, A 952
Standard power, kW 1049
Maximum power, kW 1050
Rated current per Miner, A 10
Inlet cable The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase:
L1 single core cable 600kcMil(300mm²)x4
L2 single core cable 600kcMil(300mm²)x4
L3 single core cable 600kcMil(300mm²)x4
N Single-core cable 600kcMil(300mm²)x4
PE single-core cable 500kcMil(240mm²)x2
Connection interface (Cooling tower) DN125(GB/T 9119-2010 PN16 DN125)
Connection interface (Plate heat exchange interface) DN100(GB/T 9119-2010 PN16 DN100)
Flow rate, m³/h >85
Quantity of ANTSPACE powered by one 2500kVA Transformer 2

Specification Details For Plate Heat Exchanger
Product Overview Value

Type Plate Heat Exchanger
Dimensions(L*W*H), mm 775*480*1069
Material TI

Detailed Characteristics Value
Shipping Weight, kg 379
Operating Weight, kg 461
Connection Interface DN100(GB/T 9122-2010 PN16 DN100)
External circulation supply liquid temperature, ℃ 0~30
External circulation flow rate, m³/h 33~110
Internal circulation flow rate, m³/h 100
| Points For Attention

 